Heat transfer enhancement by metal foam during nucleate pool boiling of refrigerant/oil mixture at a wide range of oil concentration
文献类型:期刊论文
作者 | Zhu Y; Hu HT; Ding GL; Zhuang DW; Peng H(彭浩) |
刊名 | HVAC&R RESEARCH
![]() |
出版日期 | 2012-05-06 |
卷号 | 18期号:3页码:377-389 |
通讯作者邮箱 | glding@sjtu.edu.cn |
关键词 | Copper-Foam R-114-Oil Mixtures Open Cells Convection Surfaces Smooth Tubes Water |
ISSN号 | 1078-9669 |
产权排序 | [Zhu, Yu;Hu, Haitao; Ding, Guoliang; Zhuang, Dawei] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China; [Peng, Hao] Chinese Acad Sci, Inst Mech, Key Lab Micrograv, Natl Micrograv Lab, Beijing 100190, Peoples R China |
通讯作者 | Ding, GL ; Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Dongchuan Rd 800, Shanghai 200240, Peoples R China. |
合作状况 | 国内 |
中文摘要 | Nucleate pool boiling heat transfer characteristics of refrigerant/oil mixtures on metal foam covers were experimentally investigated at a wide range of oil concentrations. The refrigerant and oil are R113 and VG68, respectively;and the oil concentration varies from 0% to 40%. The copper foams have pores per inch (ppi) of 10 and 20 and porosity from 90% to 98%. Experimental conditions include a saturation pressure of 101 kPa (14.696 psi), and heat flux from 30 to 137 kW m(-2) (2.6417 to 12.064 Btu s(-1) ft(-2)). The experimental results indicate that the nucleate pool boiling heat transfer coefficients on copper foam covers are larger than those on a plain heating surface by a maximum of 450%; the presence of oil deteriorates the nucleate pool boiling heat transfer on copper foam covers by a maximum of 90%. With the increase of oil concentration, the deterioration effect on high ppi metal foams is more obvious than that for low ppi. A correlation for predicting the nucleate pool boiling heat transfer coefficient of refrigerant/oil mixtures on metal foam covers is developed, and it agrees with 90% of the experimental data within a deviation of +/- 30%. |
学科主题 | 制造工艺力学 |
分类号 | Q3 |
收录类别 | SCI ; EI |
资助信息 | The authors gratefully acknowledge the support of National Nature Science Foundation of China (50906048) and China Postdoctoral Science Foundation (20090460618) for this study. |
原文出处 | http://dx.doi.org/10.1080/10789669.2012.623565 |
语种 | 英语 |
WOS记录号 | WOS:000305250300008 |
公开日期 | 2013-01-18 |
源URL | [http://dspace.imech.ac.cn/handle/311007/46585] ![]() |
专题 | 力学研究所_国家微重力实验室 |
推荐引用方式 GB/T 7714 | Zhu Y,Hu HT,Ding GL,et al. Heat transfer enhancement by metal foam during nucleate pool boiling of refrigerant/oil mixture at a wide range of oil concentration[J]. HVAC&R RESEARCH,2012,18(3):377-389. |
APA | Zhu Y,Hu HT,Ding GL,Zhuang DW,&Peng H.(2012).Heat transfer enhancement by metal foam during nucleate pool boiling of refrigerant/oil mixture at a wide range of oil concentration.HVAC&R RESEARCH,18(3),377-389. |
MLA | Zhu Y,et al."Heat transfer enhancement by metal foam during nucleate pool boiling of refrigerant/oil mixture at a wide range of oil concentration".HVAC&R RESEARCH 18.3(2012):377-389. |
入库方式: OAI收割
来源:力学研究所
浏览0
下载0
收藏0
其他版本
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。