Energy Efficient Control of Parallel Variable-Frequency Pumps in Magnetic Water-Cooling System
文献类型:期刊论文
作者 | Qiu, Wenjun![]() ![]() |
刊名 | JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME
![]() |
出版日期 | 2020-02-01 |
卷号 | 142 |
关键词 | parallel pumps variable frequency efficiency off-rating conditions optimal control energy-saving |
ISSN号 | 0098-2202 |
DOI | 10.1115/1.4044983 |
通讯作者 | Qiu, Wenjun(chouwj@hmfl.ac.cn) |
英文摘要 | This paper presents an optimal control method for the prediction of parallel centrifugal variable frequency pump performance in any conditions to maximize the total efficiency of the pump system, thereby minimizing energy consumption. First, a theoretical model of parallel water pumping set was established, after which the shaft power model was setup specifically for the off-rating conditions. By combining the typical polynomial fitting method of the efficiency and the shaft power model we brought up, a new optimized control method was proposed. Using this method, the complex optimization task was solved with the optimal control of the operating number selection and speed ratios for parallel variable speed pumps based on the decision-making. The proposed method was subsequently applied to the pumping set of the water-cooling system in High Magnetic Field Facility. The practical testing results of the proposed method showed its superiority over both the primitive and the previous optimal methods, by considerably lowering the power consumption and accurately calculating the performance parameters in any conditions. The method has universality and simplicity for online implementation, which provides a reference for the control methods of parallel centrifugal pumps in variable flow systems with a differential pressure control strategy. |
WOS关键词 | OPTIMIZATION ; WORKING |
资助项目 | High Magnetic Field Laboratory, Chinese Academy of Sciences |
WOS研究方向 | Engineering |
语种 | 英语 |
WOS记录号 | WOS:000522416800013 |
出版者 | ASME |
资助机构 | High Magnetic Field Laboratory, Chinese Academy of Sciences |
源URL | [http://ir.hfcas.ac.cn:8080/handle/334002/103623] ![]() |
专题 | 中国科学院合肥物质科学研究院 |
通讯作者 | Qiu, Wenjun |
作者单位 | Chinese Acad Sci, High Field Magnet Lab, 350 Shushan Hu Rd, Hefei 230031, Anhui, Peoples R China |
推荐引用方式 GB/T 7714 | Qiu, Wenjun,Ouyang, Zhengrong. Energy Efficient Control of Parallel Variable-Frequency Pumps in Magnetic Water-Cooling System[J]. JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME,2020,142. |
APA | Qiu, Wenjun,&Ouyang, Zhengrong.(2020).Energy Efficient Control of Parallel Variable-Frequency Pumps in Magnetic Water-Cooling System.JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME,142. |
MLA | Qiu, Wenjun,et al."Energy Efficient Control of Parallel Variable-Frequency Pumps in Magnetic Water-Cooling System".JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME 142(2020). |
入库方式: OAI收割
来源:合肥物质科学研究院
浏览0
下载0
收藏0