Conventional and advanced exergy analyses of an air-conditioning system in a subway station
文献类型:期刊论文
作者 | Yin, Hua2,3![]() ![]() |
刊名 | INTERNATIONAL JOURNAL OF EXERGY
![]() |
出版日期 | 2019 |
卷号 | 29期号:2-4页码:236-262 |
关键词 | conventional and advanced exergy analyses air-conditioning system subway station |
ISSN号 | 1742-8297 |
通讯作者 | Guo, Huafang(guohf@ms.giec.ac.cn) |
英文摘要 | Air-conditioning systems in subway stations consume a large amount of energy. In this study, conventional and advanced exergy analyses were carried out to determine the energy-saving potential of an air-conditioning system in a subway station. Results show that air handling unit (AHU) should be improved for the highest values of relative irreversibility (RI) with conventional exergy analysis, whereas the compressor should have the highest improvement priority for the largest avoidable exergy destruction with advanced exergy analysis. Moreover, influences of compressor efficiency, condensation temperature, and evaporation temperature on avoidable exergy destruction of the air-conditioning system were also investigated. According to the findings, compressor efficiency significantly influences the system's total avoidable exergy destruction. The lower the compressor efficiency, the more rapidly the avoidable exergy destruction of the compressor increases. Furthermore, the avoidable exergy destruction of condenser, compressor, cooling tower (CT), and cooling water pump (CWP) increases with the rise of the condensation temperature, whereas that of the evaporator, throttling valve (TV), condenser, compressor, CT, and CWP decreases with the rise of the evaporation temperature. |
WOS关键词 | CARBON-DIOXIDE ; ENERGY ; DESTRUCTIONS ; OPTIMIZATION ; PLANT ; CYCLE ; HVAC |
资助项目 | Guangdong Science and Technology Program[2017A020216006] ; Guangdong Science and Technology Department |
WOS研究方向 | Thermodynamics ; Energy & Fuels |
语种 | 英语 |
WOS记录号 | WOS:000473551500007 |
出版者 | INDERSCIENCE ENTERPRISES LTD |
资助机构 | Guangdong Science and Technology Program ; Guangdong Science and Technology Department |
源URL | [http://ir.giec.ac.cn/handle/344007/25306] ![]() |
专题 | 中国科学院广州能源研究所 |
通讯作者 | Guo, Huafang |
作者单位 | 1.Guangzhou Metro Grp Co Ltd, Tower A,Wansheng Sq,1238 Xingang East Rd, Guangzhou 510330, Guangdong, Peoples R China 2.Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China 3.Guangdong Key Lab New & Renewable Energy Res & De, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China 4.Guangdong Univ Technol, Sch Automated Inst, Waihuan West Rd, Guangzhou 5100006, Guangdong, Peoples R China |
推荐引用方式 GB/T 7714 | Yin, Hua,Guo, Huafang,Tang, Zhihua,et al. Conventional and advanced exergy analyses of an air-conditioning system in a subway station[J]. INTERNATIONAL JOURNAL OF EXERGY,2019,29(2-4):236-262. |
APA | Yin, Hua,Guo, Huafang,Tang, Zhihua,Yu, Junyan,&Lu, Haiyang.(2019).Conventional and advanced exergy analyses of an air-conditioning system in a subway station.INTERNATIONAL JOURNAL OF EXERGY,29(2-4),236-262. |
MLA | Yin, Hua,et al."Conventional and advanced exergy analyses of an air-conditioning system in a subway station".INTERNATIONAL JOURNAL OF EXERGY 29.2-4(2019):236-262. |
入库方式: OAI收割
来源:广州能源研究所
浏览0
下载0
收藏0
其他版本
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。