Numerical modelling and parametric study of an air-cooled desiccant coated cross-flow heat exchanger

文献类型:期刊论文

作者Liu, Lin4,5; Zeng, Tao5; Huang, Hongyu5; Kubota, Mitsuhiro3; Kobayashi, Noriyuki3; He, Zhaohong5; Li, Jun3; Deng, Lisheng2,5; Li, Xing5; Feng, Yuheng1,2
刊名APPLIED THERMAL ENGINEERING
出版日期2020-03-25
卷号169页码:16
关键词Numerical modeling Solid dehumidification Cross-flow heat exchanger Desiccant coated heat exchanger Air conditioning
ISSN号1359-4311
DOI10.1016/j.applthermaleng.2020.114901
通讯作者Huang, Hongyu(huanghy@ms.giec.ac.cn) ; He, Zhaohong(hezh@ms.giec.ac.cn)
英文摘要Air-cooled desiccant coated cross-flow heat exchanger (DCCFHE) system provides a simple and effective approach to improve dehumidification performance by using cooling air to remove adsorption heat during adsorption process. In this study, a novel numerical model validated by experimental data was established to predict the performance of a conventional silica gel DCCFHE system. The fin efficiency, as a variable due to the release of adsorption heat, was taken into account in the model. Parametric study for various air velocity and structural parameters was conducted to reveal their effects on the dehumidification performance. Results show that the smaller process air velocity is conducive to improve dehumidification performance, but the performance increases with the increase in cooling air velocity. Compared to the operation case without cooling air, the moisture removal capacity and dehumidification coefficient of performance can obtain about 35% improvement at the cooling air velocity of 1 m/s. The results also indicate that thicker desiccant layer thickness and smaller fin pitch improve moisture removal capacity and dehumidification coefficient of performance but result in greater total pressure drop Delta P, while the performance is insensible to fin thickness and fin height. Besides, effect of heat transfer performance in dehumidification and cooling sides on dehumidification performance was also analyzed. It was found that the heat transfer performance in dehumidification side is the dominant factor affecting dehumidification performance.
WOS关键词PERFORMANCE ; DEHUMIDIFICATION ; WHEEL ; MASS
资助项目Science and Technology Program of Guangzhou, China[2016201604030014] ; Shanghai Rising-Star Program, China[17QB1400900] ; Shanghai Rising-Star Program, China[17QC1401000] ; China Scholarship Council[CSC.201804910599]
WOS研究方向Thermodynamics ; Energy & Fuels ; Engineering ; Mechanics
语种英语
WOS记录号WOS:000520949000021
出版者PERGAMON-ELSEVIER SCIENCE LTD
资助机构Science and Technology Program of Guangzhou, China ; Shanghai Rising-Star Program, China ; China Scholarship Council
源URL[http://ir.giec.ac.cn/handle/344007/26842]  
专题中国科学院广州能源研究所
通讯作者Huang, Hongyu; He, Zhaohong
作者单位1.Shanghai Boiler Works Co Ltd, Shanghai 200245, Peoples R China
2.Tongji Univ, Thermal & Environm Engn Inst, 1239 Siping Rd, Shanghai 200092, Peoples R China
3.Nagoya Univ, Chikusa Ku, Furo Cho, Nagoya, Aichi 4648603, Japan
4.Univ Chinese Acad Sci, Beijing 100049, Peoples R China
5.Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, Guangdong Prov Key Lab New & Renewable Energy Res, 2 Nengyuan Rd, Guangzhou 510640, Peoples R China
推荐引用方式
GB/T 7714
Liu, Lin,Zeng, Tao,Huang, Hongyu,et al. Numerical modelling and parametric study of an air-cooled desiccant coated cross-flow heat exchanger[J]. APPLIED THERMAL ENGINEERING,2020,169:16.
APA Liu, Lin.,Zeng, Tao.,Huang, Hongyu.,Kubota, Mitsuhiro.,Kobayashi, Noriyuki.,...&Yan, Kai.(2020).Numerical modelling and parametric study of an air-cooled desiccant coated cross-flow heat exchanger.APPLIED THERMAL ENGINEERING,169,16.
MLA Liu, Lin,et al."Numerical modelling and parametric study of an air-cooled desiccant coated cross-flow heat exchanger".APPLIED THERMAL ENGINEERING 169(2020):16.

入库方式: OAI收割

来源:广州能源研究所

浏览0
下载0
收藏0
其他版本

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。