Experimental research on the heating performance of a single cylinder refrigerant injection rotary compressor heat pump with flash tank

文献类型:期刊论文

作者Sun JinFei1,2,3,4; Zhu DongSheng2,3,4; Yin YingDe2,3,4; Li XiuZhen1,2,3,4
刊名SCIENCE CHINA-TECHNOLOGICAL SCIENCES
出版日期2018-12-01
卷号61期号:12页码:1814-1823
关键词rotary compressor refrigerant injection DC (direct current) inverter heat pump heating performance injection pressure
ISSN号1674-7321
DOI10.1007/s11431-017-9237-6
通讯作者Zhu DongSheng(zhuds@ms.giec.ac.cn)
英文摘要A single cylinder rotary compressor was applied in the refrigerant injection air-source heat pump to improve the heating performance in cold regions. In this study, the performance of an R410A single cylinder rotary compressor vapor injection (SCRCVI) system was measured and analyzed by varying the compressor frequency f and injection pressure P-inj at the ambient temperature T-od=-10 degrees C.The experimental results indicated that an optimum injection pressure to gain the maximum COPh (coefficient of performance) existed in the SCRCVI cycle. However, the maximum COPh of the SCRCVI system decreased as the increase of the frequency, and the maximum COPh was even lower than that of the CSVC system at high compressor frequency. Therefore, in view of the energy saving and emission reduction, the SCRCVI system should be switched to single stage compression system when the heating capacity demand could be satisfied at high compressor frequency f. Compared to the conventional single-stage vapor compression (CSVC) system, refrigerant injection could enhance the heating capacities and COPh by 28.2% and 7.91%, respectively. The average total mass flow rate of the SCRCVI system was 24.68% higher than that of the CSVC system. As the SCRCVI system worked at the optimum injection pressure, the variation trends of the different system parameters were investigated in detail. These trends were reliably used to optimize the refrigerant injection system design and the control strategy. The parameter of (P-inj-P-s) could be adopted as the signals to control the opening of the upper stage electronic expansion valve EEV1.
WOS关键词SPEED SCROLL COMPRESSOR ; SYSTEM ; OPTIMIZATION ; R410A ; MODEL ; PORT
资助项目South Wisdom Valley Innovative Research Team Program ; Shunde District of Foshan City Government Office[365] ; Guangzhou Collaborative Innovation Major Projects[201604016048] ; Guangzhou Collaborative Innovation Major Projects[201604016069]
WOS研究方向Engineering ; Materials Science
语种英语
WOS记录号WOS:000453827200004
出版者SCIENCE PRESS
资助机构South Wisdom Valley Innovative Research Team Program ; Shunde District of Foshan City Government Office ; Guangzhou Collaborative Innovation Major Projects
源URL[http://ir.giec.ac.cn/handle/344007/29822]  
专题中国科学院广州能源研究所
通讯作者Zhu DongSheng
作者单位1.Univ Chinese Acad Sci, Beijing 100049, Peoples R China
2.Guangdong Key Lab New & Renewable Energy Res & De, Guangzhou 510640, Guangdong, Peoples R China
3.Chinese Acad Sci, Key Lab Renewable Energy, Guangzhou 510640, Guangdong, Peoples R China
4.Chinese Acad Sci, Guangzhou Inst Energy Convers, Guangzhou 510640, Guangdong, Peoples R China
推荐引用方式
GB/T 7714
Sun JinFei,Zhu DongSheng,Yin YingDe,et al. Experimental research on the heating performance of a single cylinder refrigerant injection rotary compressor heat pump with flash tank[J]. SCIENCE CHINA-TECHNOLOGICAL SCIENCES,2018,61(12):1814-1823.
APA Sun JinFei,Zhu DongSheng,Yin YingDe,&Li XiuZhen.(2018).Experimental research on the heating performance of a single cylinder refrigerant injection rotary compressor heat pump with flash tank.SCIENCE CHINA-TECHNOLOGICAL SCIENCES,61(12),1814-1823.
MLA Sun JinFei,et al."Experimental research on the heating performance of a single cylinder refrigerant injection rotary compressor heat pump with flash tank".SCIENCE CHINA-TECHNOLOGICAL SCIENCES 61.12(2018):1814-1823.

入库方式: OAI收割

来源:广州能源研究所

浏览0
下载0
收藏0
其他版本

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。