Analysis of Transient Operating Characteristics of the 10 Kv Tri-Axial HTS Cable Under Fault Current

文献类型:期刊论文

作者Guan, Guangyu1,2; Feng, Bin1; Ding, Kaizhong1; Zhu, Jiahui3; Wei, Defu4; Cao, Jingying5; Liu, Jiaxin4; Chen, Jie5; Du, Shuangsong1; Du, Dingqing1
刊名IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY
出版日期2021-11-01
卷号31
ISSN号1051-8223
关键词Fault current transient characteristics temperature distribution recovery time
DOI10.1109/TASC.2021.3103708
通讯作者Ding, Kaizhong(kzding@ipp.ac.cn)
英文摘要The Tri-axial high temperature superconducting (HTS) cable usually subjects to the impact of the fault currents in the power system. During the fault, a large amount of the Joule heat is generated, which may be damage cable. In this paper, an analysis model of electromagnetic thermal transient characteristics of the 10 kV/1 kA cable is built. The transient characteristics of the HTS cable are analyzed under a fault current of 15 kA rms lasting 0.14 s, and the current, resistance and temperature of the HTS cable are obtained. The maximum temperature of the HTS cable is 153.1 K under fault current. Meanwhile, the safe operating range of the HTS cable under the fault current of 15 kA to 25 kA is obtained. the analysis results will provide the theoretical basis for the quench protection and relay protection strategy of the tri-axial HTS cable in the Grid.
资助项目State Grid, China[DG71-20-006]
WOS研究方向Engineering ; Physics
语种英语
出版者IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
WOS记录号WOS:000708681200007
资助机构State Grid, China
源URL[http://ir.hfcas.ac.cn:8080/handle/334002/125643]  
专题中国科学院合肥物质科学研究院
通讯作者Ding, Kaizhong
作者单位1.Chinese Acad Sci, Inst Plasma Phys, Hefei Inst Phys Sci, Hefei 230031, Peoples R China
2.Anhui Univ, Inst Phys Sci & Informat Technol, Hefei 230601, Peoples R China
3.China Elect Power Res Inst, Beijing 100192, Peoples R China
4.State Grid Shenyang Elect Power Co Ltd, Shenyang 110006, Peoples R China
5.State Grid Jiangsu Elect Power Co Ltd, Nanjing 210000, Peoples R China
推荐引用方式
GB/T 7714
Guan, Guangyu,Feng, Bin,Ding, Kaizhong,et al. Analysis of Transient Operating Characteristics of the 10 Kv Tri-Axial HTS Cable Under Fault Current[J]. IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY,2021,31.
APA Guan, Guangyu.,Feng, Bin.,Ding, Kaizhong.,Zhu, Jiahui.,Wei, Defu.,...&Dong, Yujun.(2021).Analysis of Transient Operating Characteristics of the 10 Kv Tri-Axial HTS Cable Under Fault Current.IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY,31.
MLA Guan, Guangyu,et al."Analysis of Transient Operating Characteristics of the 10 Kv Tri-Axial HTS Cable Under Fault Current".IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY 31(2021).

入库方式: OAI收割

来源:合肥物质科学研究院

浏览0
下载0
收藏0
其他版本

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。