Control system and operational characteristics of gas engine-driven heat pump
文献类型:期刊论文
| 作者 | Lv, Jie1,4,5; Tian, Jiayao1,2,4,5; Hu, Yafei1,2,4,5; Feng, Ziping1,3,4,5; Song, Wenji1,4,5 |
| 刊名 | INTERNATIONAL JOURNAL OF REFRIGERATION
![]() |
| 出版日期 | 2023 |
| 卷号 | 145页码:148-157 |
| 关键词 | Gas engine-driven heat pumps Engine speed control Heating capacity Outlet water temperature control Waste heat recovery |
| ISSN号 | 0140-7007 |
| DOI | 10.1016/j.ijrefrig.2022.09.020 |
| 通讯作者 | Feng, Ziping(fengzp@ms.giec.ac.cn) |
| 英文摘要 | The control system is an important component of a gas engine-driven heat pump (GHP). Recent studies conducted on GHPs focus on the model construction and optimization, while neglecting the control system. This study proposes an embedded control system to monitor GHP cold-hot water equipment (GHPW). The accuracy of the control system and strategy was verified. Additionally, the operational characteristics of GHPW system based on the control system were discussed through cooling and heating experiments. The experimental results demonstrated that double closed-loop control of the engine speed and evaporator superheat via the main controller ensured stable and accurate outlet water temperature control in the GHPW system. The heating capacity of the heat pump was increased from 42.37 to 75.2 kW in the heating mode with a gradual increase in the engine speed from 1200 to 2400 rpm, while the heating capacity of the experimental system was increased from 56.18 to 105.87 kW. The waste heat recovery of the engine significantly improved the system heating capacity and primary energy ratio (ratio of GEHP heating capacity to natural gas consumption power). Additionally, the GHPW system improved energy saving. The circuits and control strategy proposed in this study are simple and easy to implement. The control system improved the performance of GHPs and reduced the peak power load during summer. |
| WOS关键词 | PERFORMANCE ; SIMULATION ; SPEED |
| 资助项目 | National Key Research and Develop-ment Program of China ; [2021YFE0112500] |
| WOS研究方向 | Thermodynamics ; Engineering |
| 语种 | 英语 |
| WOS记录号 | WOS:000897126700007 |
| 出版者 | ELSEVIER SCI LTD |
| 资助机构 | National Key Research and Develop-ment Program of China |
| 源URL | [http://ir.giec.ac.cn/handle/344007/38105] ![]() |
| 专题 | 中国科学院广州能源研究所 |
| 通讯作者 | Feng, Ziping |
| 作者单位 | 1.Chinese Acad Sci, CAS Key Lab Renewable Energy, Guangzhou 510640, Peoples R China 2.Univ Chinese Acad Sci, Beijing 10049, Peoples R China 3.ZKG Energy Chongqing Res Inst Co Ltd, Chongqing 401331, Peoples R China 4.Chinese Acad Sci, Guangzhou Inst Energy Convers, Guangzhou 510640, Peoples R China 5.Guangdong Prov Key Lab New & Renewable Energy Res, Guangzhou 510640, Peoples R China |
| 推荐引用方式 GB/T 7714 | Lv, Jie,Tian, Jiayao,Hu, Yafei,et al. Control system and operational characteristics of gas engine-driven heat pump[J]. INTERNATIONAL JOURNAL OF REFRIGERATION,2023,145:148-157. |
| APA | Lv, Jie,Tian, Jiayao,Hu, Yafei,Feng, Ziping,&Song, Wenji.(2023).Control system and operational characteristics of gas engine-driven heat pump.INTERNATIONAL JOURNAL OF REFRIGERATION,145,148-157. |
| MLA | Lv, Jie,et al."Control system and operational characteristics of gas engine-driven heat pump".INTERNATIONAL JOURNAL OF REFRIGERATION 145(2023):148-157. |
入库方式: OAI收割
来源:广州能源研究所
浏览0