中国科学院机构知识库网格
Chinese Academy of Sciences Institutional Repositories Grid
Improvement of nitrogen removal and reduction of operating costs in an activated sludge process with feedforward-cascade control strategy

文献类型:期刊论文

作者Zhang P(张平); Yuan MZ(苑明哲); Wang H(王宏)
刊名Biochemical Engineering Journal
出版日期2008
卷号41期号:1页码:53-58
关键词Activated sludge process ASM1 Dissolved oxygen concentration Feedforward control Cascade control
ISSN号1369-703X
产权排序1
中文摘要In this paper, a feedforward-cascade controller for dissolved oxygen concentration in an activated sludge process is designed in order to meet stricter effluent quality standards at a minimum cost. Conventional proportional and integral (PI) constant dissolved oxygen set-point control and feedforward-cascade dissolved oxygen set-point control are evaluated using the reduced model of activated sludge model no. 1 and reduced IWA simulation benchmark. The feedforward-cascade control has been based on a hierarchical structure where a high level or cascade control selects the set-point of the low level or conventional controller and low level directly control dissolved oxygen concentration. And feedforward control is introduced in the control system for preventing the influent loading from influencing the system. Simulation results show that feedforward-cascade control of the activated sludge process is more successful than conventional PI control in meeting the effluent standards and reducing operational costs. This control strategy can be expected to be accepted by the operating personnel in wastewater treatment plants.
WOS标题词Science & Technology ; Life Sciences & Biomedicine ; Technology
类目[WOS]Biotechnology & Applied Microbiology ; Engineering, Chemical
研究领域[WOS]Biotechnology & Applied Microbiology ; Engineering
关键词[WOS]DISSOLVED-OXYGEN CONCENTRATION ; FEEDFORWARD
收录类别SCI ; EI
语种英语
WOS记录号WOS:000257906200009
公开日期2012-05-29
源URL[http://ir.sia.cn/handle/173321/6907]  
专题沈阳自动化研究所_工业信息学研究室_工业控制系统研究室
推荐引用方式
GB/T 7714
Zhang P,Yuan MZ,Wang H. Improvement of nitrogen removal and reduction of operating costs in an activated sludge process with feedforward-cascade control strategy[J]. Biochemical Engineering Journal,2008,41(1):53-58.
APA Zhang P,Yuan MZ,&Wang H.(2008).Improvement of nitrogen removal and reduction of operating costs in an activated sludge process with feedforward-cascade control strategy.Biochemical Engineering Journal,41(1),53-58.
MLA Zhang P,et al."Improvement of nitrogen removal and reduction of operating costs in an activated sludge process with feedforward-cascade control strategy".Biochemical Engineering Journal 41.1(2008):53-58.

入库方式: OAI收割

来源:沈阳自动化研究所

浏览0
下载0
收藏0
其他版本

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。